Permit Number: TC-RES-0925-04334
Parcel: 125072190

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0925-04334
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/05/2025 Addressing Validation REQUIRES RESUBMIT ATTENTION: Parcel/addressing issue. The site plan shows to be for an ADU. The location, 527 N Nortan AV, does not have units attached to the address or parcel. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit. After address/units have been added or verified you'll need to submit an address change request (REQUEST CHANGE OF ADDRESS) to update this permit application and resubmit all plans/documents that show the corrected address . For questions: Building_Official@tucsonaz.gov
09/29/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0925-04334
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

GENERAL COMMENTS :

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.

SECTIONS - DETAILS:

1. Clarify if the separating wall between dwelling and garage is fire rated in compliance with R302.6. Show a ½” gypsum board or equivalent on each side of a framed wall or CMU.
2. Clarify the thermal envelope. Show the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show the water heater location, P2801.1.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. Provide a minimum service conductor rating of #3 copper 75 degree C for the 100 AMP feeder, E3602.1 & E3603.1. Update the feeder wire size on the main panel schedule.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
09/09/2025 Site Engineering - Standard REQUIRES RESUBMIT Permit: TC-RES-0925-04334 •
Location: 527 N NORTON AV
Review Date: 9/9/2025
Site Engineering Comments:
1. Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf), all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in Sections 402-404 of the ADA Accessibility Standards (https://www.access-board.gov/ada/chapter/ch04/). See TSM 7-01.4.3 for specifications, including slope and composition materials.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/03/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Claire Leighou, Planner

PROJECT: TC-RES-0925-04334

527 N NORTON AV UNIT 2

Convert Guest House into ADU (first review)

TRANSMITTAL DATE: 10/3/25



Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

The ADU Code Amendment section on the cover sheet references outdated code. See Unified Development Code (UDC) Section 6.6.3. Ensure compliance with Section 6.6.3.B.6., “the minimum side and rear yard setback for an ADU is 5 ft.”

Please draw, dimension, and label setbacks from all structures to all applicable property lines

Please add the zoning classifications of the surrounding properties to the site plan, which are R-1 to the north, west, and south, and R-2 to the east.



The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code



If you have any questions about this transmittal, please contact Claire Leighou at claire.leighou@tucsonaz.gov. Thank you!
09/05/2025 PDSD Application Completeness Express REVIEW COMPLETED