Permit Number: TC-RES-0924-05566
Parcel: 117066320

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0924-05566
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2024 Site Zoning APPROVED
10/25/2024 Site Engineering NOT REQUIRED
10/29/2024 Site Landscape NOT REQUIRED
10/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/10/2024 Residential Building REQUIRES RESUBMIT TC-RES-0924-05566
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with the updated construction plan set.

SITE PLAN:

1. The east wall is placed within the 3-foot fire separation distance from the neighboring property line. Show fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by protecting the structure placed within 3 feet of the property line in compliance with IBC Table 721.1(2).

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. (Mini split, extend duct from a central HVAC or an electrical base board heater.

ELECTRICAL PLANS:

1. Designate the correct circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1. Change #14 on the plan to #28 as shown on the panel schedule.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
09/25/2024 PDSD Application Completeness REVIEW COMPLETED