Permit Number: TC-RES-0924-05458
Parcel: 128061280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0924-05458
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/01/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0924-05458 (841 S VAN BUREN AV TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems
When applying for a permit to place new equipment on existing code-compliant roofs, an allowance shall be provided for equipment weighing a maximum of 4 psf and load per attachment point of 45lbs or less. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Development%20Services/Building/Equipment%20on%20roofs%20.pdf
3. Provide calculations showing total roof equipment weight is a maximum per attachment point of 45lbs or less. R324.4.1.1

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/23/2024 Site Engineering REQUIRES RESUBMIT TC-RES-0924-05458
841 S VAN BUREN AV

Comments for Site Engineering are as follows:
1. This project is within a regulated floodplain, Arcadia Wash, and requires a Floodplain Use Permit (FUP.)

Please start a new FUP at our permit application web page:
https://tdc-online.tucsonaz.gov/#/home

NOTE: A cost estimate of materials and labor from your contractor in the form of a pdf attachment will be required to complete the FUP application. Please have separate lines for cost of materials, and cost of labor. Thank you.

Ryan Insalaco
Engineering Associate
City of Tucson
Planning & Development Services Department
Email: ryan.insalaco@tucsonaz.gov
Phone: (520) 837-5351
09/22/2024 PDSD Application Completeness REVIEW COMPLETED