Permit Number: TC-RES-0924-05445
Parcel: 135090800

Address:
7626 E LERMA PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0924-05445
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2024 Site Zoning APPROVED
09/24/2024 Fire New Construction NOT REQUIRED
10/21/2024 Site Engineering NOT REQUIRED
10/04/2024 Site Landscape NOT REQUIRED
10/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/02/2024 Residential Building REQUIRES RESUBMIT TC-RES-0924-05445
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Provide a response letter on separate file with the updated construction plan set.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Revise the electrical load calculations following Table E3602.2 for sizing the general usage loads. The demand may be less than 200 AMP.
2. Provide a panel schedule showing breakers sized for protecting the wire size rather than showing the demand, E3601.6.1 & E3706.2. Refer to Table E3705.5.3 for sizing 15-, 20- & 30-AMP branch circuit conductors and protection ratings.
3. Show the dishwasher/disposal with 20A breaker, E3703.8.
4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
5. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
09/20/2024 PDSD Application Completeness Express REVIEW COMPLETED