Permit Number: TC-RES-0924-05408
Parcel: 11450016C

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0924-05408
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0924-05408 (8499 E WOODLAND RD TUCSON, AZ 85749)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. There is an existing permit with a similar scope of work, TC-RES-0624-03584 (8499 E WOODLAND RD TUCSON, AZ 85749). This permit shows an existing 1200A service. Please have this permit withdrawn and clarify the service rating.


Electrical Requirements:

2. Per COT submittal requirements: A service upgrade to 600A requires a design by a Arizona Registered Electrical engineer. A Registered Electrical Engineer is required when electrical designs exceed 400 amps, and where the available fault current at any new piece of equipment exceeds 22,000 amps. IBC 107.1.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

3. Arizona Revised Statute R4-30-302 - A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.

• Electrical Plans Fully dimensioned floor plan showing location and assigned circuit numbers of all outlets, luminaires, switches, appliances, panels, motors, disconnects, electrical and HVAC equipment. All home runs should indicate panel name or number.
• One Line Diagram Include voltage and phase, Panel and/or transformer size, Feeder loads, rating breakers or fuses including A.I.C., Complete fault current analysis and total tenant and building service load
• Panel Schedule Include panel numbers, voltage, phasing, location, bus size, circuit number, breaker sizing, number of poles, A.I.C rating, number of lights and/or receptacles by circuit, total KVA load.

Gas Line review:
4. For a new gas line addition, modification to the gas line or increase in gas demand, you will need to provide a complete gas pipe plan for sizing compliance verification. G2412.3, G2412.4

5. Modification to the gas line system and meter, require the submission of a gas pipeline template, G2401.1, R301.1: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_piping_template_1.pdf
See also: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf
6. Provide a complete gas piping template showing the connection from the meter to all gas appliances, include all future connections/demand to the new gas line. Include pipe size, type and length. Provide appliance demands. G2413.4.1

7. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) (Polyethylene Plastic Pipe).
8. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/18/2024 PDSD Application Completeness Express REVIEW COMPLETED