Permit Number: TC-RES-0924-05408
Parcel: 11450016C

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0924-05408
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2024 PDSD Application Completeness Express REQUIRES RESUBMIT Unable to process. Not all review comments were addressed with your submittal:

Electrical Requirements: >>> City of Tucson and the State of Arizona regulations require modifications to services over 400A to be prepared and sealed by a qualified and registered Electrical Engineer. Also, TEP being able to supply 600A does not confirm that the existing equipment is rated to support the 600A.

Per COT submittal requirements: A service upgrade to 600A requires a design by a Arizona Registered Electrical engineer. A Registered Electrical Engineer is required when electrical designs exceed 400 amps, and where the available fault current at any new piece of equipment exceeds 22,000 amps. IBC 107.1.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

Arizona Revised Statute R4-30-302 - A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.

Gas Line review: >>> Although this gas line is for future use, you still need to submit a gas plan to show the gas line size, type, etc.

For a new gas line addition, modification to the gas line or increase in gas demand, you will need to provide a complete gas pipe plan for sizing compliance verification. G2412.3, G2412.4

Modification to the gas line system and meter, require the submission of a gas pipeline template, G2401.1, R301.1: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_piping_template_1.pdf

Please resubmit your plans, other supporting permit documents and a written response Letter to each of the notated items, indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received for addressing all comments left.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions:building_official@tucsonaz.gov