Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0924-05392
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/17/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0924-05392 (4112 S FERRIS DR TUCSON, AZ 85730) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide a complete line diagram of the electrical connections. Show connections from generator to ATS, MSP and sub/backup panel. 2. The location of the generator on the sitemap does not appear to show the same location as on the other document. The generator exhaust must be 10 feet from any air intake openings of any dwelling and 6 feet from the property line, R303.5.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
09/17/2024 | PDSD Application Completeness | REVIEW COMPLETED |