Permit Number: TC-RES-0924-05212
Parcel: 132110530

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0924-05212
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/11/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0523-05052 (2530 S 2ND AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

Provide an electrical line diagram identifying each relevant component and circuit, notating sizes and installation details.
Clarify what you mean by "Re-run load center feeder with 50 amp".
Provide a minimum service conductor rating of 100 AMP for each dwelling and conductors with minimum rating of #4 copper 75 degree C, E3602.1 & E3603.1.
09/10/2024 PDSD Application Completeness Express REVIEW COMPLETED