Permit Number: TC-RES-0924-05187
Parcel: 112052420

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0924-05187
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2024 Light Residential Building Review (OIP) APPROVED
10/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/10/2024 Site Engineering REQUIRES RESUBMIT TC-RES-0924-05187
2932 N JACKSON DR

Site engineering comments are as follows:
1. Because this development is in a floodplain, it will require a Floodplain Use Permit. Be sure to upload a PDF of the cost estimate with the FUP application as this is a Residential Solar addition.

Ryan Insalaco
Engineering Associate
City of Tucson
Planning & Development Services Department
Email: ryan.insalaco@tucsonaz.gov
Phone: (520) 837-5351
10/07/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0924-05187
2932 N JACKSON DR. – R-1
PV ROOF MOUNT + SOLAR CARPORT STRUCTURE (1st Review)

TRANSMITTAL DATE: October 7, 2024

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9

Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Where the wall meets the eave of the roof.

1. Based on a wall height of 9’-0” or less the required perimeter yard setback for the proposed carport structure to the north property line is 6’-0”. Per UDC Article 6.4.5.B.2 the setbacks for a carport type structure are measured from the post supporting the structure as long as the roof overhang does not exceed 2’-0”, UDC Article 6.4.5.D.1.b. Based on roof overhang of 3’-10” and the allowed 2’-0” roof overhang and the 6’-9” setback dimension the proposed setback to the north property line from the allowed 2’-0” overhang is 4’-11”. It is not clear if the carport structure is attached to the main dwelling. If this structure is not attached a neighbors setback waiver may be used to reduce the required setback, UDC Article 6.6.2.D . To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
If the structure is attached or you are not able to secure the waive then a Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

2. Show the allowed 2’-0” roof overhang on the plan and provide a setback dimension from both the north and west property line to the 2’-0” overhang on the plan, UDC Articles 6.4.5.D.1.b & 6.4.5.D.2.a.(2).

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/10/2024 PDSD Application Completeness Express REVIEW COMPLETED