Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0924-05128
Parcel: 221351440

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0924-05128
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2024 PDSD Application Completeness Express REQUIRES RESUBMIT Site plan insufficient. Site plan does not show the exact location of the electrical panel. If using Google aerial, please ensure settings are in terrain to show all existing structures on the property. Please resubmit a proper site plan, with address of the project, the exact location of the electrical panel including all circuiting information, OCPD, conductor type and size, conduit, etc, and all existing structures on the property. The conductors underground must comply with E3803.1 and be rated for use in a conduit in a wet location, E3803.10 i.e. THWN
Also, this is an electrical work only application. Spa install will need separate permit.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf If you have any further questions or concerns you can reach me at building_official@tucsonaz.gov.