Permit Number: TC-RES-0924-05111
Parcel: 133350280

Address:
964 N BEDFORD DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0924-05111
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2024 Site Engineering NOT REQUIRED
10/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/20/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0924-05111 (964 N BEDFORD DR TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The calculations for the backfeed fuse sizing, on sheet PV-4, are wrong. Please update the calculations to show the correct total current from the (N) 100A Dedicated Load Center.
2. The conductors from the (N) 100A Dedicated Load Center are undersized for the total design current of 83.2A. Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25). Reference NEC 690.8(A)(3) and (B)(1) for conductor sizing.
3. Update Conductor sizing and calculations on sheet PV-5 for Raceway # 4-6.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/05/2024 PDSD Application Completeness Express REVIEW COMPLETED