Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0924-05111
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2024 | Site Engineering | NOT REQUIRED | |||
| 10/04/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/20/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0924-05111 (964 N BEDFORD DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. The calculations for the backfeed fuse sizing, on sheet PV-4, are wrong. Please update the calculations to show the correct total current from the (N) 100A Dedicated Load Center. 2. The conductors from the (N) 100A Dedicated Load Center are undersized for the total design current of 83.2A. Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25). Reference NEC 690.8(A)(3) and (B)(1) for conductor sizing. 3. Update Conductor sizing and calculations on sheet PV-5 for Raceway # 4-6. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/05/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |