Review Details: RESIDENTIAL SOLAR v.2
Permit Number - TC-RES-0924-05111
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/04/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0924-05111 (964 N BEDFORD DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Plans still show Solaredge optimizers, not the correct micro-inverters. 2. The conductors out of the 2x Enphase Combiner Boxes are missing sizing info. 3. The Fused disconnect is undersized for the total design current as shown in the calculations I’ve marked on the plans. 4. The wire schedule on sheet PV-5 is incomplete and shows the wrong conductor sizes coming out of the 125A dedicated load center. 5. EOR’s Seal is missing from the relevant structural pages. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||