Permit Number: TC-RES-0923-08447
Parcel: 133540090

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0923-08447
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/02/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-08447 (1056 S SUNCOVE DR TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The maximum demand for the 18kw generator is 247 cubic feet per hr. The 1” gas pipe is undersized for this demand. See Table G2413.4(1), length 70’. Minimum required gas line, BIP, 1 ¼”.
2. Provide a complete electrical line diagram showing all components, conductor size/type, OCPDs and ratings, E3402.3, E3403.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/02/2023 PDSD Application Completeness Express REVIEW COMPLETED