Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0923-08436
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/09/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-0923-08436 Resubmit comment: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. 1. Due to the relocation of the meter and the rerouting of the external pipe the internal piping is undersized per table G2413.4(1). 2. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. 3. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. Provide measurements for each segment of the pipe. 4. Your plans show a âTâ for a future use. List the demand this future use will use. G2413.2 Contact Ramiro with any questions: Ramiro.olivarez@tucsonaz.gov |
||
10/09/2023 | PDSD Application Completeness | REVIEW COMPLETED |