Permit Number: TC-RES-0923-08436
Parcel: 136390410

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0923-08436
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/29/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC)
General comment:
1. Moving the location of the Gas Meter may cause existing gas pipe systems to become undersized and could require additional modifications to be code compliant, G2412.3.
PLUMBING Plans:
1. Note and specify all piping materials and sizes, P2609.
2. Provide a gas piping plan showing the connection from the meter to ALL attached appliances. Include pipe size, type and length. Show connection, lengths and sizes, from gas meter to all gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, , G2413.1, R301.1: See https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
3. Provide manufacturer’s spec sheet demonstrating Appliance fuel input or use prescriptive number in gas piping template, R106.1.1.
4. Provide total demand from all appliances, G2413.2.
5. Use G2413.4.1 to determine the required developed length to be used in sizing tables.
a. G2413.4.1 Longest length method: Length is from Meter to the furthest connected appliance. Use this same length to determine all pipe sizes.
6. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe).
7. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
8. Minimum burial depth, 12”, G2415.12.
9. Yellow tracer wire required for non-metallic pipe, G2415.17.3.
09/29/2023 PDSD Application Completeness REVIEW COMPLETED