Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0923-08255
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/02/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0923-08255 (969 N MILLER DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. The manufacturer’s specification sheet for the A1-BI-200-G2 Backup Interface shows a maximum current from/to the grid, and to the main panel as 160A. The Plans show an input from/to the grid and to the main panel at 200A. Clarify and show a connection to the grid and main panel that meets the spec sheet requirements. R102.4, R106.1.2. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/22/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |