Permit Number: TC-RES-0923-08170
Parcel: 130031800

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0923-08170
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/22/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-08170 (1521 S BRISTOL AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

Having the panelboard above the gas meter is not code compliant.

1. Provide a panelboard clear working space of 30” wide x 36” deep, E3405.2. This clearance space is from the ground to a height of 6.5’, Figure E3405.1 footnote b.
2. Show all electrical equipment a minimum distance of 3’ from the gas meter regulator vent. https://www.swgas.com/1409187404208/Gas-Meter-Reqs.pdf

3. Show on the site plan or a floor plan of the house, where the new circuits are being placed, R106.1.1. Detail the wire type, size and OCPD being used, E3401.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/22/2023 PDSD Application Completeness Express REVIEW COMPLETED