Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0923-08168
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/21/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0923-08168 (712 S MAGNOLIA AV TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide updated plans that show the Main Service Panel in code compliance for solar interconnection, 2017 NEC requirements found in section 705.12(B)(2)(3) b Busbars. 120% bus bar rule. You can find the solar planset here. https://pro.tucsonaz.gov/permitdetails/T18CM05601/. 2. Provide the Main Service Panel specification sheet for code compliance verification, R106.1.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/19/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |