Permit Number: TC-RES-0923-08138
Parcel: 133280390

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0923-08138
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/19/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-08138 (8411 E COLETTE ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Size the pipe based on the length from the meter to the farthest attached appliance and max demand of each branch using Table G2413.4(1) (Metallic Pipe). Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
2. The ¾” pipe is undersized for the given length and demand. Use Table G2413.4(1), Row 70’, demand = 170 and demand = 135. 1” pipe is required for all 3/4” segments.
3. The ½” pipe to the furnace is undersized. Requires ¾” pipe.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov