Permit Number: TC-RES-0923-08127
Parcel: 126062140

Address:
4021 E 4TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0923-08127
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/11/2023 Residential Building REQUIRES RESUBMIT TC-RES-0923-08127
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Consider using a design professional if unfamiliar with construction documentation.

Separate the support documents from the construction plans. Place sheet numbers on each sheet of construction plans.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

Provide a site plan showing the location of all buildings and utilities, R106.1.1. Show the location of all utility lines to the proposed building(s) along with required service alterations.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window openings in the proposed space. Both proposed and altered bedrooms must show code compliance for egress, R310.

SECTIONS - DETAILS:

1. Provide a structure section showing existing and proposed features including a foundation, sills, anchoring, framing, sheathing and insulation, R106.1.
2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3. Clarify the placement of ceiling/roof insulation for determining the need for an attic ventilation calculation or need for providing air-impermeable rigid insulation at the roof for condensation control, R806.
4. Show an unvented roof assembly with all insulation at the roof including an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total insulation requirement, R806.5 or show the attic vent opening size using 1 to 150 of attic area with insulation at the ceiling in compliance with R806.2.

MECHANICAL PLANS:

1. Show heating/cooling facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
2. Show a smoke alarm in each bedroom and outside the doorway in the immediate vicinity, R314.3.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

OUTDOOR LIGHTING CODE

Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
09/21/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-RES-0923-08127
4021 East 4th Street – R-1
Carport enclosure (1st Review)

TRANSMITTAL DATE: September 21, 2023

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

The site is in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in the R-1 zone, subject to use-specific standards 4.9.7.B.5-.9.

1. Remove any porches and patios from the lot coverage calculation as roofed areas, open on at least one, which provide shelter to exterior areas, provided they are not used for utilities, maintenance, laundry, storage, or motor vehicle parking, are excluded from the lot coverage calculation (UDC 6.4.3.C.1.a). The “existing sidewalk area” is also not included within total lot coverage.

2. Show the five-foot-wide easement along the north lot line as depicted on the Alvernon Addition Subdivision Plat (https://maps-and-records.tucsonaz.gov/subdivisions/details/MP-07081&).

3. Provide a floor plan of the existing residence to demonstrate compliance with use-specific standard 4.9.7.B.7. For any new single-family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. For all single-family dwellings in the R-1 zone with five or more bedrooms, all parking spaces must be located on-site, either in a side or rear perimeter yard. Parking spaces may not be located in a vehicular use area in any front street perimeter yard.

Per UDC 11.4.3, the term “bedroom” includes all of the following: 1) Any room that is designated as a bedroom; 2) Any enclosed room that has a minimum area of 60 square feet and has an accessible opening to the exterior of the building in compliance with the International Building Code (IBC), whether termed a studio, family room, study, den, bonus room, or any other name, except for a living room, diming room, kitchen, and bathrooms; and 3) Any room designated as a bedroom for the purpose of any other code requirement.

If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
09/20/2023 PDSD Application Completeness REVIEW COMPLETED
09/22/2023 Site Engineering REVIEW COMPLETED