Permit Number: TC-RES-0923-08007
Parcel: 11009019D

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0923-08007
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/20/2023 Historic REQUIRES RESUBMIT Property is a designated historic resource within the Fort Lowell Multiple Resource area and any exterior changes require review. Please include all items noted under Minor review in the Historic & Special Districts information handout (https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf).
Additionally, on the site plan, note the location of the units. Include information on the height of the parapet and the height of the proposed units. Once all required information is assembled, please resubmit under the Historic sub-record.
09/19/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-08007 (5425 E FORT LOWELL RD TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The addition of the new to the gas fired HVAC, requires the submission of a gas pipeline template (or equivalent), G2401.1, R301.1: https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
See also: https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
Provide a gas piping plan showing the connection from the meter to the all gas fired appliances. Include pipe size, type and length. Provide HVAC unit’s gas demands. G2413.4.1.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max demand of each branch using Table G2413.4(1) (Metallic Pipe). Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
3. The addition and relocation of the units may require the existing gas piping to be upsized to meet currently adopted codes.
4. Show the location of the new and relocated units on the site-plan, R106.1.1.
5. Provide a floor plan to show new duct work. Provide a duct system sized in accordance with Manual D calculations, M1601.1.
6. Clarify the Trane Model Numbers being used. The Manual-j forms for the two Trane models appears to show different model numbers than the model numbers in the Air Conditioning installation Templates, R106.1.1.
7. Show a WP GFCI receptacle outlet on the same level within 25’ of all exterior HVAC equipment, E3901.12.
8. The Permit for the 400A service upgrade is incomplete, Permit: TC-RES-0623-05677. This service upgrade permit needs to be completed in order to show the 400A service in this permit.
9. Show the location of any additional work done as referenced in Case T22DV05587.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/20/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-RES-0923-08007
5425 E FORT LOWELL RD Zoning HRX-2

TRANSMITTAL DATE:‎September 20, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HRX-2 zone (UDC 4.7.9). Historic Review is required. Please submit a special districts application as a sub-record of this permit. The submittal requirements and instructions can be found below. Please contact Jodie Brown (jodie.brown@tucsonaz.gov) or Michael Taku (michael.taku@tucsonaz.gov) for any questions. Zoning can not approve until the historic review has been approved.

https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/special_districts_application_instructions-1.pdf

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
09/19/2023 PDSD Application Completeness REVIEW COMPLETED Permit will be in review only for the address listed on the application, customer will need to submit a permit application for each unit.