Permit Number: TC-RES-0923-07971
Parcel: 11502151B

Address:
621 E ELM ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0923-07971
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/12/2025 Residential Building REQUIRES RESUBMIT TC-RES-0923-07971 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

PLANS:

1. Provide an engineer’s calculation, design, and seal for a performance design is required when minimum sizes are not code compliant with the IRC, R301.1. Include the foundation requirements and identification of all fasteners.

SECTIONS - DETAILS:

1. The structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by enhancing the structure placed within 3 feet of the property line in compliance with IBC Table 721.1(2). Include a one hour rated wall below the roof edge with foundation along the full length of structure near the property line or relocate the structure outside of the fire separation distance.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
08/25/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section
PROJECT: TC-RES-0923-07971
621 E ELM ST Zoning - R-2
Patio Roof (2nd Review)

TRANSMITTAL DATE:‎ August 25, 2025

COMMENTS: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.
1. COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf This shall in include:
a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. Lot coverage must include vehicular use area whether improved or unimproved, see UDC Article 6.4.3.B.3.b.
b. Provide a dimension from the center line of Elm St to the face of curb, where pavement meets the concrete curb, and from face of curb to the south property line. Per Construction Plan I-468, sheet 10, found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-468, The distance from centerline to face of curb is 17’, and from face of curb to south property line is 8’.
c. Pe UDC Article 6.4.5.B.2 perimeter yard setbacks to a porch or carport type structure are measured from the post supporting the roof structure as long as the roof overhang is not more than 2’-0”, UDC Article 6.4.5.D.1.b and 6.4.5.D.2.A.(5). Clearly show the post supporting the proposed roof structures along with overhang dimensions and provide perimeter yard setback dimensions on the site plan.
d. The “FRONT SETBACK 10.00’” shown on the site plan is not correct. Per UDC Article 6.4.5.C.1.a, the required front street perimeter yard setback is 20’.
e. The “REAR SETBACK 10.00’” shown on the site plan is not correct. Per UDC Table 6.3-2.A the minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line.

2. Based on what few perimeter yard setbacks are provided it appears that a Design Development Option (DDO) will need to be processed and approved to reduce the setbacks. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/planning-amp-zoning/2019_ddo_for_setback_and_height_udc.pdf . The completed application shall be submitted as a PDF under assigned permit number . If you have questions about the DDO application or process please contact Wyatt Berger at wyatt.berger@tucsonaz.gov or Georgia Pennington at georgia.pennington@tucsonaz.gov.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/08/2025 PDSD Application Completeness Express REVIEW COMPLETED