02/26/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Replace the conductor between the disconnect and the meter-collar with #6 conductor size as it is sized at #10 and is too small. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4.