Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0923-07917
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/26/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Replace the conductor between the disconnect and the meter-collar with #6 conductor size as it is sized at #10 and is too small. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4. Building_official@tucsonaz.gov |
||
| 02/12/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |