Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0923-07906
Parcel: 126131180

Address:
4620 E 14TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0923-07906
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2023 Site Engineering NOT REQUIRED
11/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2023 Residential Building REQUIRES RESUBMIT 1. Notate or detail interior wall and ceiling covering (1/2” GWB), R702.3.
2. Show the ceiling gypsum board as either 5/8” or ½” sag resistant when applied to 24” o/c ceiling framing, IRC table R702.3.5 footnote d.
3. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2.
11/02/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0923-07906
4620 E. 14th St. – R-1
2 Bedroom Addition (1st Review)

TRANSMITTAL DATE: November 2, 2023

Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence w/sleeping quarters is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.
.
1. The plans should be submitted as a single multi-page pdf file.

2. The lot coverage calculation is not correct. Per UDC Article 6.4.3.B.3.b, all vehicle use areas, whether improved or unimproved, concrete driveways, are included in the coverage.

3. Based on aerial photos there is an addition to the carport, north end, that shows up sometime after 2008. Zoning was not able to find approved permit documents for this addition. Either provide approved permit documents or include the carport addition in this permit.

4. The minimum setback to the front street perimeter property line is twenty (20) feet ((UDC 6.4.5.C.1.a), proposed street perimeter yard setback is 4’-9”.

5. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As dimensions to design grade were not provided on the elevations Zoning has added 6” to the dimensions provide. Based on a wall height of 13’-1” the required perimeter yard setback to the west property line is 8’-9”, proposed setback is 6’-3”. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/23/2023 PDSD Application Completeness Express REVIEW COMPLETED