Permit Number: TC-RES-0923-07905
Parcel: 138041840

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0923-07905
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2023 Site Engineering NOT REQUIRED
09/20/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/20/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-07905 (617 W CALLE LERDO TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. TEP usually requires the service panel on the property at the closest building to the service transformer. You may need to work with TEP to provide a safe and code compliant location for the service equipment. The overhead service conductor over the unpermitted shed roof requires an 8’ clearance above the shed roof, E3604.2.1 (can be reduced depending on the slope of the shed roof, see exception 2). The necessary mast height at the existing panel location may not be a feasible installation.
2. Tucson Electric Power requires meters and associated equipment to be relocated from under patios when the service is upgraded or the space is closed-in, TEP SR-405.10.L. The unpermitted shed appears to close-in the space around the service equipment.
3. Provide a panelboard clear working space of 30” wide x 36” deep, E3405.2. This could not be verified due to the location of the unpermitted shed.
4. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov