Permit Number: TC-RES-0923-07896
Parcel: 130070740

Address:
3650 E 23RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0923-07896
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2023 Site Zoning APPROVED
09/11/2023 Site Engineering NOT REQUIRED
09/21/2023 Site Landscape NOT REQUIRED
09/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/26/2023 Residential Building REQUIRES RESUBMIT TC-RES-0923-07896
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

SITE PLAN:

Show the electrical line between buildings as underground rather than overhead, R106.1.1.

SECTIONS - DETAILS:

1. Show the wall assembly with a 6” clearance above the ground (between F.F. & F.G.), R317.1 item 5. Update detail #1/A102. The minimum clearance between weep screed and grade is 4” (or 2” clearance above an exterior concrete surface) which is a different requirement.
2. An unvented roof assembly requires air-impermeable rigid insulation material of a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total R-38 insulation requirement, R806.5. Also, the batt insulation is required to completely fill the framed cavity for correct contact to the air barrier. Update the roof insulation shown at detail #1/A203.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the airflow rate setting and update the NOTE: 1. Addressing the general requirement (3rd from bottom sheet A206). A two or three bedroom sleeping quarters under 1501 SF requires a 45 CFM continuous setting.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services