Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/08/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0923-07888 (4533 E MONTECITO ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Each address will require a separate permit. You will need to file for a permit for 4535 E MONTECITO ST. Each permit can only cover work done at one address.
2. Provide clarification on the scope of work. The description states that you will “Add an electrical service to the property”, but the provided plans appear to show the new electrical work connected to 2 existing service panels. Are you adding a 3rd service to the property, or connecting into the existing services.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2. Highlight all new circuits being added.
4. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
5. Use Table E3705.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3705.4.1.
6. Show all carport and storage 120 volt receptacle outlets 15 & 20 AMP with GFCI protection, E3902.2.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/08/2023 PDSD Application Completeness Express REVIEW COMPLETED It appears the site plan uploaded lists 2 addresses and each individual address requires its own permit. This permit is for (4533 E MONTECITO ST) only, please start new permits for the other address.