Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0923-07887
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2023 | Site Engineering | NOT REQUIRED | |||
| 09/20/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/20/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0923-07887 (3836 E DOVER SV TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Utility Disconnect shows fuse at 30A, see sheet PV 5 and PV 6. Design current is 66.25A. Show Overcurrent Protection fuses sized according to 2017 NEC 690.8(A) and (B). 2. For a Line Side connection, provide a NG-Bond in the Utility Disconnect. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/11/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |