09/11/2023 Site Engineering NOT REQUIRED
09/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/22/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-0923-07836 Resubmit comment:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Sheet PV-4, 6-gauge wire from the meter to the lineside tap is too small. Update it as shown on Sheet PV-5.

2. DG Disconnect 60A fuse is too small and needs to be upsized.