Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0826-04847
Parcel: 123022120

Address:
2549 E LINDEN ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04847
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2026 PDSD Application Completeness Express REVIEW COMPLETED
08/28/2026 Light Residential Building Review (OIP) Express VOID If you have questions regarding this Review, please email at
PDSD-Permits@tucsonaz.gov
This permit application will be voided. It appears there is a duplicate permit application (TC-RES-0826-04680). Please see all review comments and resubmit under the existing permit, TC-RES-0826-04680, and include both addresses on the aerial view. Please also provide the model number of the SPD to be installed. The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, per 230.67.
Resubmittal Instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

Address request Instructions:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf