Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0826-04811
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/28/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment and resubmit along with a comment response letter: 1) Provide the manufacturer's specifications identifying the Minimum Circuit Ampacity (MCA) and Maximum Overcurrent 2) Protection (MOCP). Branch-circuit conductors and overcurrent protection must be in accordance with 440.6(A), 440.22, and 440.32. 3) Provide a disconnecting means within sight of and readily accessible from the outdoor condensing unit, 440.14. 4) Equipment requiring service must be GFCI protected 210.8( E), E3902.13 |
||
| 08/28/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |