Permit Number: TC-RES-0826-04811
Parcel: 110180190

Address:
2810 N RALPH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04811
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/28/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment and resubmit along with a comment response letter:
1) Provide the manufacturer's specifications identifying the Minimum Circuit Ampacity (MCA) and Maximum Overcurrent
2) Protection (MOCP). Branch-circuit conductors and overcurrent protection must be in accordance with 440.6(A), 440.22, and 440.32.
3) Provide a disconnecting means within sight of and readily accessible from the outdoor condensing unit, 440.14.
4) Equipment requiring service must be GFCI protected 210.8( E), E3902.13
08/28/2026 PDSD Application Completeness Express REVIEW COMPLETED