Permit Number: TC-RES-0826-04784
Parcel: 136342790

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.2

Permit Number - TC-RES-0826-04784
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Provide a comment response letter and address the following comments:
1) Please correct interconnection method, plans note 705.11(A) for supply side which does not reflect interconnection on plan set.
2) Registrant must stamp the plan set if you wish to adhere to interconnection requirements using 705.12(B)(6). Otherwise provide the details below for 705.12
a) Feed through conductors and OCPD from the 200A bus supplying the 100A lower bus must be sized in accordance with 705.12(A)(2).
b) The sum of supply sources (95A) exceeds the maximum allowable capacity (40A) for the 200A busbar. The main breaker rating plus all back fed breakers must not exceed 120% of the busbar rating per NEC 705.12(B)(2)
c) Provide load calculations including the Tesla metering device for the 100A bus bar (Standard or Optional are accepted) 220.10
09/25/2026 PDSD Application Completeness Express REVIEW COMPLETED