Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.2
Permit Number - TC-RES-0826-04784
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/25/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) Please correct interconnection method, plans note 705.11(A) for supply side which does not reflect interconnection on plan set. 2) Registrant must stamp the plan set if you wish to adhere to interconnection requirements using 705.12(B)(6). Otherwise provide the details below for 705.12 a) Feed through conductors and OCPD from the 200A bus supplying the 100A lower bus must be sized in accordance with 705.12(A)(2). b) The sum of supply sources (95A) exceeds the maximum allowable capacity (40A) for the 200A busbar. The main breaker rating plus all back fed breakers must not exceed 120% of the busbar rating per NEC 705.12(B)(2) c) Provide load calculations including the Tesla metering device for the 100A bus bar (Standard or Optional are accepted) 220.10 |
||
| 09/25/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |