Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0826-04780
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/02/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this Review, please email at PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: 1) Submit a Change of Address Request to include unit number to permit application Address request instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf |
||
| 09/02/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: 1) Please provide the model # of the SPD to be installed, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 |
||
| 09/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |