Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0826-04706
Parcel: 131020270

Address:
5402 E 28TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04706
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/26/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) The 3/4" ug poly pipe is undersized for the given length and appliance demand. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) (Polyethylene Plastic Pipe), or Manufacturer’s sizing requirements.
Please revise the pipe size or verify demand of appliances matches with those listed on the gas template.

Note: Approximate distances of appliances is relevant to determine if the sizing of the fuel gas line from the meter is compliant. Provide this upon resubmittal
08/25/2026 PDSD Application Completeness Express REVIEW COMPLETED