Permit Review Detail
Review Status: In Review
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0826-04694
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Residential Engineering | PENDING ASSIGNMENT | |||
| N/A | Residential Zoning | PENDING ASSIGNMENT | |||
| 08/27/2026 | Residential Building | REQUIRES RESUBMIT | TC-RES-0826-04694 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. SCOPE OF REVIEW: The scope of this plan review includes architectural, plumbing, mechanical, energy conservation and electrical compliance with the 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings. Provide a separate response letter addressing each comment with location of change on the plans. GENERAL COMMENTS: 1. Update the address (215 S SENTINEL PEAK) appearing at the top of sheet L3-CS and on the title block of each sheet. PLANS: 1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. The threshold condition may be located at the garage/dwelling doorway or at an exterior hinged door. Update keynote #30b on sheet L11-2 or include the appeal number. 2. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Habitable spaces, laundry/utility rooms, garages and basements require automatic shutoff control for turning off lighting within 20 minutes after occupants leave the space, IECC R404.2. Please contact the plans reviewer if you have any questions: Kenneth.VanKarsen@tucsonaz.gov City of Tucson Residential Building Safety |
||
| 08/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |