Permit Number: TC-RES-0826-04661
Parcel: 134110420

Address:
7926 E 19TH PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04661
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this Review, please email at PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
The address on the permit application and aerial view do not match. Please revise address on aerial view. If the address on the permit application needs to be changed, submit a Change of Address Request to update address. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf
08/21/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1) Clearly show panel location; this applies even if the location will remain the same.
2) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
08/21/2026 PDSD Application Completeness Express REVIEW COMPLETED