Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.3
Permit Number - TC-RES-0826-04634
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/02/2026 | Restamp Residential Building | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) The SPD provided Eaton BRPSURGE has a 3 kA nominal discharge rating, this device does not comply with the requirement in E3606.5 or 230.67 nor match PV4 nor PV5 equipment description. Please provide the spec sheet of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 2) This permit is only for Unit 2 (existing Man. Home) |
||
| 09/01/2026 | Addressing Validation | REVIEW COMPLETED | |||
| 09/01/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |