Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: TC-RES-0826-04595
Parcel: 133250600

Address:
8627 E 3RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0826-04595
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) The SPD provided HOM2175SB has a 5 kA nominal discharge rating, this device does not comply with the requirement in E3606.5 or 230.67. Please provide the model # of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
08/21/2026 PDSD Application Completeness Express REVIEW COMPLETED