Permit Number: TC-RES-0826-04553
Parcel: 11708285A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0826-04553
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Residential Zoning APPROVED
08/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/19/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact PDSD-Permits@tucsonaz.gov

Parcel/addressing issue. The site plan shows to be for a duplex. The location does not have units attached to the address. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit numbers. After address/units have been added or verified you'll need to submit an address change request to update this record in the sub records tab of the permit along with a new aerial/site plan that shows the corrected addressing.
08/20/2026 Residential Building REQUIRES RESUBMIT TC-RES-0826-04553
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review includes architectural, plumbing, mechanical, energy conservation and electrical compliance with the 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Provide a separate response letter addressing each comment with location of change on the plans.

GENERAL COMMENTS:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
2. Plans submitted for a newly constructed one- or two-family dwelling after June 1, 2010, require gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. The ordinance revision now requires a gray drain line discharge from one fixture for a one-story dwelling. Additional gray fixture drains are optional. Show a dual clothes washer standpipe with a black connection and a gray line plumbed to an exterior wall above grade when feasible, or a bathing fixture drain looped 3’ beyond an exterior wall below grade before connection to the building drain. Use the appropriate detail at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Water-Energy-Conservation Gray Water Illustrations
3. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021 and 2024 IRC appendix NE. Include a 40 ampere 240-volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space.

SITE PLAN:

1. Show the location of a single sewer HCS for the property coordinated with Pima County Wastewater, R106.1.1. https://www.pima.gov/1766/Wastewater-Reclamation
2. Each dwelling building requires a street address and a separate permit, R319. Show Pima County assigned unit numbers at each dwelling on the site plan.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. The threshold condition may be located at the garage/dwelling doorway or at an exterior hinged door.
2. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.
3. Individual dwelling units require separation with a 1-hour fire-resistance rated assembly without opening extended to the roof, R302.3. Update Section #1 on sheet A-4.0.
4. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic ventilation and calculation is shown on A-3.0 but an unvented roof assembly with R-5 rigid insulation material is shown on A-4.0. Show a consistent roof design with insulation types and minimum thickness for meeting the condensation control requirement. A vented design requires a minimum 1” air gap from the eave openings to the ridge. Ridge venting would also reduce the total open area by one half.
2. Batt insulation may not be in contact with the roof sheathing, R806.5. Clarify detail #6 on A-5.0 with either a 1” gap between insulation and roof desk or show a layer of R-5 rigid at the roof deck.

PLUMBING PLANS:

1. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1.
2. Show the water heater rating/capacity for consistence with the electrical circuit size, R106.1.1.

ELECTRICAL PLANS:

1. Show the Electric Vehicle Supply Equipment 40 ampere 240-volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.
2. Specify the Electric Vehicle NEMA 14-50R receptacle at a parking area, N1104.2.1.
3. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
4. Refer to Table E3705.5.3 for sizing 15-, 20- & 30-AMP branch circuit conductors and protection ratings. Show appropriate wire sizes and update circuit #10/12.
5. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
10. HVAC equipment after September 1, 2026. E3902.14.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Specify high-efficacy luminaires with an efficacy not less than 45 lumens per watt or lamps with efficacy not less than 65 lumens per watt (LED devices), IECC R404.1. Remove the percentage limits from note #32.
2. Habitable spaces, laundry/utility rooms, garages and basements require automatic shutoff control for turning off lighting within 20 minutes after occupants leave the space, IECC R404.2.

Please contact the plans reviewer if you have any questions:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
08/28/2026 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0826-04553
Project: Duplex
Location: 928 S BEAN AV
Review Date: 8/28/2026

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter review time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

Provide a response letter addressing each comment with location of change on the plans. Submit the separate response letter and plan set files.

1. Per the City of Tucson Inclusive Home Design Ordinance https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf, all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”.
a. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in 2017 ICC A117.1 Sections 402-403, including the minimum 4ft-width, slope and composition materials.
b. Label the accessible entrances on the site plan.
2. Please review and address Building comments.

If you have any questions or concerns, please contact Joe Macaulay at: Joe.Macaulay@tucsonaz.gov
08/19/2026 PDSD Application Completeness Express REVIEW COMPLETED