Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) The SPD listed on the plans (Eaton BRNSURGE) is not code compliant with the nominal discharge current rating (In) requirement. SPD must be 10kA In per E3606.5.4 and 230.67 (E)
08/17/2026 PDSD Application Completeness Express REVIEW COMPLETED