Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADU v.1

Permit Number - TC-RES-0826-04503
Review Name: RESIDENTIAL ADU v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/17/2026 Residential Building REQUIRES RESUBMIT Provide a complete construction plan set showing 2024 IRC and City of Tucson building ordinance compliance after DDO approval.
08/19/2026 Residential Engineering REQUIRES RESUBMIT Permit Activity Number: TC-RES-0826-04503 (1st Review)
Project: ADU
Location: 5798 E CAMINO DE AZUCAR Unit: UNIT 1
Review Date: 8/19/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway) all the way to a usable door of the home — one that someone using a wheelchair or mobility aid could navigate without barriers. An exterior accessible route that shall conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance. The current plans to no reference a material nor show a connection to ROW sidewalk or Parking area proposed. Ensure dimension the path at the minimum 4-feet required.
Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf
Action Items — Show the following on your plans:
• Draw and label the path as "Accessible Route"
• Provide a minimum clear width of 4 feet with a width call-out on the plans
• Note the proposed running slope (must not exceed 5% / 1:20) and cross slope (must not exceed 2% / 1:50)
• Identify the accessible entrance the route leads to

Acceptable Accessible Route compositions include:
• Portland cement concrete (PCC)
• Broom Finished concrete
• Brick or unit pavers (Only if set on a stable cement base with no gaps exceeding ½”)
• Concrete pavers on concrete base (Same joint and evenness requirements as brick)
• Flagstone: must be mortared – loose set does not qualify
• Any surfaces equivalent in smoothness, hardness, and durability
NOTICE: Decomposed granite (DG) is not permitted for required accessible routes, even if compacted
08/19/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Claire Leighou, Planner

PROJECT: TC-RES-0826-04503

5798 E CAMINO DE AZUCAR UNIT 1

Detached ADU (1st Review)

TRANSMITTAL DATE: 8/19/26

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). An ADU is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

Comment 1: Based on plat maps for the area, it appears the required minimum setback for side and rear yards is 3’. Two of the proposed setbacks on the site plan show 2’9”. Please either adjust the location of the proposed ADU to meet the minimum of 3’ from side/rear property lines, or begin the process of a Board of Adjustment variance process to allow the reduced setback. For additional information regarding variances, please contact Mark Castro at Mark.Castro@tucsonaz.gov

Comment 2: Please draw, dimension, and label the distance between the primary house and the proposed ADU at the closest corner of the existing house.

Comment 3: Please provide landscaping details on the plan upon next submission. Per UDC 7.6.8.A, all new single family, middle housing, and accessory dwelling unit development requires the following landscaping:

One canopy tree for every 1,000 square feet of gross floor area. For projects below 1,000 SF, this number should be rounded up to one tree added.

Vegetative groundcover is required within the front yard setback per the calculation below.

(X Linear feet of Street Frontage) - (Y Curb cut width) x (5 Foot Depth) = Z Square Feet of vegetative groundcover

Additional details on landscaping requirements may be found in the zoning code here: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-6131

The list of allowable trees/groundcover plants may be found here: https://www.azwater.gov/sites/default/files/media/TAMA2015LWUPL_0.pdf

Comment 4: Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf), all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Please draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in Sections 402-404 of the ADA Accessibility Standards (https://www.access-board.gov/ada/chapter/ch04/). See TSM 7-01.4.3 for specifications, including slope and composition materials.

Comment 5: Please draw, dimension, and label all vehicular use area(s) on the site, including driveways and any additional parking spaces. Please include this area in the lot coverage calculations.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code

If you have any questions about this transmittal, please contact Claire Leighou at claire.leighou@tucsonaz.gov. Thank you!
08/17/2026 PDSD Application Completeness Express REVIEW COMPLETED