Permit Number: TC-RES-0826-04434
Parcel: 130083240

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04434
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/10/2026 Light Residential Building Review (OIP) Express PENDING ASSIGNMENT
08/10/2026 PDSD Application Completeness Express REQUIRES RESUBMIT If you have questions regarding the PDSD Application Completeness Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please submit a comment response letter demonstrating compliance with the following requirement:
1) The submitted site plan does not identify the specific address associated with this permit application. Please revise the site plan to clearly indicate the location being addressed to allow for proper review.
2) If the service panel supplying 100% of the electrical load to a dwelling is installed/replaced, it must adhere to 230.67. A SPD must be listed on the plans, this device must be a Type 1 or 2, UL 1449 Listed, and have a nominal discharge rating of at least 10kA.