Permit Number: TC-RES-0826-04407
Parcel: 118035370

Address:
2770 W SHERYL DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0826-04407
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2026 Residential Zoning APPROVED
08/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/19/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) A Surge Protection Device (SPD) or SPD model number must be identified on the plans for all service panel replacements supplying 100% of the dwelling. This requirement can be satisfied by providing the manufacturer’s specifications or model number for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
2) Bollards are not required for this ESS Installation as it is not within a drivable portion on the property R330.8. However, include specifications and plans for the bollards adhering to 330.8.3.1 if the installation of bollards will remain
08/10/2026 PDSD Application Completeness Express REVIEW COMPLETED