Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0826-04392
Parcel: 134070270

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0826-04392
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/10/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) Please provide the model # of the SPD to be install, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
08/10/2026 PDSD Application Completeness Express REVIEW COMPLETED