Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/07/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1) Please resubmit and provide a site plan or an aerial view (from above) photograph with the address. If there is no new work. Include a note on plan stating "No new work. Electrical Reconnect Only"
2) If modifications are being made to the panel, please provide a description of the work (e.g., upgrade: 200-amp service, etc.).Be sure to show the proposed location of the scope of work, this applies even if the location will remain the same.
A Surge Protection Device (SPD) must also be identified on the plans. This requirement can be satisfied by providing the manufacturer's specifications for the SPD to verify that it is UL listed and code-compliant, per E606.5 and NEC 230.67.
08/07/2026 PDSD Application Completeness Express REVIEW COMPLETED