Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0826-04335
Parcel: 13112024B

Address:
5911 E 30TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0826-04335
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact
PDSD-Permits@tucsonaz.gov

Previous comment was not addressed. Please resubmit addressing the following comment:
1) Please provide the specifications of the Surge Protection Device (SPD) to be installed, this can be done by showing the data sheet provided by the manufacturer or by listing the model number of the individual device. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
08/25/2026 PDSD Application Completeness Express REVIEW COMPLETED