Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.4
Permit Number - TC-RES-0826-04308
Review Name: RESIDENTIAL ADD/ALT v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/20/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please address the previous comment, no attic venting calculations or rigid insulation are present on the plans. Please clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. |
||
| 10/14/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |