Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/20/2026 Residential Building - Standard REQUIRES RESUBMIT Please address the previous comment, no attic venting calculations or rigid insulation are present on the plans.

Please clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.