Permit Number: TC-RES-0826-04283
Parcel: 123052860

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADU v.1

Permit Number - TC-RES-0826-04283
Review Name: RESIDENTIAL ADU v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/04/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact PDSD-Permits@tucsonaz.gov

Parcel/addressing issue. The site plan shows to be for an ADU (Accessory Dwelling Unit). The location does not have units attached to the address. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the units. After address/units have been added or verified you'll need to submit an address change request to update this record along with a new aerial/site plan that shows the corrected addressing.
08/05/2026 Residential Building REQUIRES RESUBMIT TC-RES-0826-04283
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Provide a separate response letter addressing each comment with location of change on the plans.

GENERAL COMMENTS:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Show the utility meters and lines from the utility source to the building, R106.1.1. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions.
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1.
3. Provide a complete roof framing plan with beams and rafters sized with appropriate prescriptive load carrying capacity, R301.1 or provide an engineer’s sealed plan set for performance compliance consideration, R301.1.3.
4. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Provide a wall section detail with reinforced foundations for anchoring exterior framed walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Show exterior wood siding, sheathing, water-resistive barrier and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
3. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1.
2. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.
3. Identify the device model number providing an adjustable setting and note the minimum continuous or intermittent setting for providing whole-house mechanical ventilation, R303.4; N1103.6 & M1505.4.

PLUMBING PLANS:

1. The Tucson Water Department limits flow rates for the water meter size in compliance with P2903.7. Show an appropriate yard pipe size with connection between the existing dwelling and the meter.
2. Show an individual accessible water supply shut off and water heater for the proposed dwelling unit, P2903.9.1.
3. Show the water heater rating/capacity for consistence with the electrical circuit size, R106.1.1.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a service disconnect for both the primary and ADU dwelling (location site specific), E3403. Show the ADU feeder size and appropriate breaker requirement, E3602.1 & E3603.1.
2. Provide a minimum service conductor rating of #3 copper 75 degree C for the 100 AMP feeder, E3602.1 & E3603.1.
3. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
4. Receptacles may not be located at the exterior face of island cabinets where below the countertop. Either provide a vertical assembly listed for countertop (work surface) mounting, or a raceway terminated within the cabinet for future assembly installation, E3901.4.2.
5. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
10. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026, E3902.14.
6. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.20. Add notation to plans.

OUTDOOR LIGHTING CODE

1. Show the proposed exterior fixtures as full cut-off (FCO) style for eliminating the need for an Outdoor Lighting Calculation.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
08/19/2026 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0826-04283
Location: 2350 E JUANITA ST
Review Date: 8/19/2026
A Comment Response letter is required. Please address all reviewer’s comments in a separate document with all required documents for resubmittal.

Residential Engineering Comments:
1. Project is in a City of Tucson Flood Hazard Zone associated with the Wilson Avenue Wash and will require an elevation certificate. Please include BFE and FFE on next submittal. A floodplain use (FPU) permit has been started for the project (TE-FPU-0826-00336). Follow the instructions related to the FPU permit.
2. Please include the limits of the Wilson Avenue Wash floodplain on the site plan sheet.
3. Due to the property location within floodplain limits, the new detached dwelling must be built to floodplain standards. Show the finished floor elevation (FFE) on the construction site plan (sheet 1). Based on a calculated base flood elevation (BFE) of 2425.36-FT NAVD88, and a regulatory finished floor must be (at a minimum) FFE = 2426.36-FT NAVD88. Please provide the FFE of the proposed detached dwelling on the construction site plan.
4. The elevation of the building pad and FFE will be conducted by a registered surveyor, and the completed elevation certificates must be submitted to TE-FPU-0826-00336 for review and approval.
5. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway). NOTE: the exterior accessible route must conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance. Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf
6. Please review and address zoning comments. Due to zoning constraints the location of the structure may change, if the structure location may change or detached ADU becomes attached, please contact Site-Engineering@tucsonaz.gov.

If you have any questions or concerns, please contact Joe Macaulay. Joe.Macaulay@tucsonaz.gov
08/06/2026 Residential Zoning REQUIRES RESUBMIT FROM: Drew Szentesy
Planner

PROJECT: TC-RES-0826-04283
2350 E Juanita St., Tucson, AZ 85719
ADU
TRANSMITTAL DATE: 08/06/2026

This site is located within the R-1 zone (UDC 4.7.8). An accessory dwelling unit (ADU) is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .8, & .12 and 6.6.3.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.
Draft:
1. Please add building heights for the accessory dwelling unit and primary single-family residence to your site plan.
2. Please include vehicle use area (including driveways) in lot coverage calculations (UDC Section 6.4.3.B.3.b).
3. Per UDC 6.6.3.C. standard, detached accessory buildings, including accessory dwelling units, are not permitted in the buildable area extending the full width of the lot between the principal building and front street lot line. To leave the accessory dwelling unit in its current state, would require a Board of Adjustment Variance. Zoning cannot approve this permit until the Board of Adjustment (B/A) Variance Process is completed and approved. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov
4. Per UDC 6.4.5.C.1.a, the minimum required front street perimeter yard is 20 feet measured from the street property line and your proposed front street perimeter yard setback is 5ft. This will require a second variance but can be applied for under the same Variance Process as the above comment.
5. Per UDC 6.6.3.B.11, accessory dwelling units must follow the landscaping standards in UDC 7.6.2.C. New Single Family, Middle Housing, and ADUs. Please ensure site conformance with these standards are demonstrated on the site plan in the next submittal.

The City of Tucson Unified Development Code may be accessed here: www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .

If you have any questions about this transmittal, please contact Drew Szentesy at Drew.Szentesy@tucsonaz.gov
08/04/2026 PDSD Application Completeness Express REVIEW COMPLETED