Permit Number: TC-RES-0825-04194
Parcel: 136191400

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0825-04194
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT PDSD Residential Review Section
PROJECT: TC-RES-0825-04194 Installation of new 1.5 ton mini split system-(1st Review) (8057 E NICARAGUA DR )
TRANSMITTAL DATE: August 25th, 2025

Comments:
1. On the AC Installation Template, please clarify location of new equipment (Template shows both Ground Mount and Flat Roof). If new equipment location is roof, please also complete the Rafter/Joist Support information on the Template.

2. Please submit a site plan or aerial photograph showing the location of work.

3. Please provide electrical load calculations for determining that the service panel can support the additional electrical load, E3602.2 and a panel schedule showing wire size and OCPD of each new circuit, E3702.2.

Please email any questions to: Building_Official@tucsonaz.gov
08/25/2025 PDSD Application Completeness Express REVIEW COMPLETED