Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESTAMP - RESIDENTIAL v.1
Permit Number - TC-RES-0825-03985
Review Name: RESTAMP - RESIDENTIAL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/25/2025 | Residential Building Express | REQUIRES RESUBMIT | Please resubmit once corrections have been made to the plans. 1.Specify the “R” value of the insulation, as well as the “U” factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.40, SHGC=0.25, ceiling R=38 and walls R=13. 2. Notate that air inlets be located a minimum of 10’ from vent openings or exhaust outlets (unless the outlet is 3 feet above the air inlet), M1602.2.1 and G2427.8. 3.Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans |